Welcome to FOWRISE!
Welcome to FOWRISE!

Commercial Heaing and Cooling Air Source Heat Pump

An all-scenario heating and cooling solution designed for modern commercial complexes, hotels, and office spaces. Utilizing air as the thermal source and water as the heat transfer medium, a single system seamlessly meets both winter heating and summer cooling needs; it serves as a perfect replacement for the redundant configurations of traditional boilers and air conditioning units, significantly reducing mechanical room footprint and initial investment costs.

Share:

Commercial Heaing and Cooling Air Source Heat Pump

An all-scenario heating and cooling solution designed for modern commercial complexes, hotels, and office spaces. Utilizing air as the thermal source and water as the heat transfer medium, a single system seamlessly meets both winter heating and summer cooling needs; it serves as a perfect replacement for the redundant configurations of traditional boilers and air conditioning units, significantly reducing mechanical room footprint and initial investment costs.

 

💎Features:

1) Extended working range down to -35°C ambient (low ambient type)

2) Heating+Cooling

3) Low running costs and high efficiency

4) Long-life and corrosion resistant composite cabinet stands up to severe climates

5) Famous compressor ensures outstanding performance and durability

6) LCD touch screen with self-diagnostic control function

7) Automatic defrosting

8) Easy operation and simple installation

9) WIFI control function is optiona

 

💎Specifications:

Model FKH20BD FKH25BD FKH30BD FKH50BD
Heating
(A7℃/W45℃)
Heating Capacity kW 58.0 65.0 75.0 130.0
Power Input kW 18.0 20.0 21.4 40.0
COP 3.5 3.3 3.5 3.3
Nominal heating
(Fan coil)
(A-12℃/W41℃)
Heating Capacity kW 39.0 42.0 48.0 84.0
Power Input kW 17.0 19.0 21.0 38.0
COP 2.3 2.2 2.3 2.2
Nominal heating
(Floor Heating)
(A-12℃/W35℃)
Heating Capacity kW 38.0 44.0 53.0 88.0
Power Input kW 16.0 18.0 20.5 36.0
COP 2.4 2.4 2.6 2.4
Nominal heating
(Radiators)
(A-12℃/W50℃)
Heating Capacity kW 38.0 43.0 52.0 86.0
Power Input kW 18.0 21.5 26.0 43.0
COP 2.1 2.0 2.0 2.0
Low temperature heating
(Fan coil)
(A-20℃/W41℃)
Heating Capacity kW 30.0 34.0 42.0 64.0
Power Input kW 16.5 18.0 22.0 36.0
COP 1.8 1.9 1.9 1.8
Low temperature heating
(Floor Heating)
(A-20℃/W35℃)
Heating Capacity kW 30.0 34.0 41.0 64.0
Power Input kW 15.0 17.0 19.5 34.0
COP 2.0 2.0 2.1 1.9
Low temperature heating
(Radiators)
(A-20℃/W50℃)
Heating Capacity kW 30.0 34.0 44.0 68.0
Power Input kW 18.0 20.5 26.0 41.0
COP 1.7 1.7 1.7 1.7
Rated cooling
(A35℃/W7℃)
Cooling Capacity kW 45.0 52.0 60.0 104.0
Power Input kW 18.0 20.0 23.0 40.0
EER 2.5 2.6 2.6 2.6
Max Power Input kW 25.0 28.0 33.0 58.0
Max Running Current A 37.9 42.4 50.0 87.9
Power Supply / 380-415V/3N~/50Hz
Ambient Temperature Range  -35 ~ 43ºC
Electric Shock Proof Grade / Class I
Protection Grade / IPX4
Refrigerant Type -/kg R410A/R32
Noise-Cooling dB/(A) 65 68 69 70
Noise-Heating dB/(A) 66 69 70 71
Max. Outlet Water Temp. °C 60 60 60 60
Rated Water Flow m³/h 12 15 18 30
Outlet Water Pipe Connector inch DN50 DN50 DN50 DN65
Compressor Highly/Copeland
Water Side Heat Exchanger Plate Heat Exchanger
Air Side Heat Exchanger Inner threaded pipe + Hydrophilic Aluminum Fin Heat Exchanger
4-Way Valve Sanhua
Electronic Expansion Valve Sanhua
Shell Materials Galvanized steel with powder coating
Controller 4-inch Colored Touch Screen
Wi-Fi Function Yes
Dimension (L*W*H) mm 1310*1100*2030 1310*1100*2030 1310*1100*2030 2300*1310*2322
Net Weight kg 400 450 470 950