When a heat pump does not perform as expected, many people immediately suspect the compressor.But in many cases, the compressor is not the real problem.

Insufficient water flow, blocked filters, incomplete defrosting, inaccurate sensors, and circulation pump problems can all affect heating performance and system reliability.For installers, HVAC contractors, and service technicians, understanding the correct troubleshooting sequence is therefore essential.


1. Outlet Water Temperature Is Too Low

Typical Symptom

The heat pump is running, but the actual outlet water temperature is lower than the setpoint or the required project temperature.

Possible Causes

  • Outlet water temperature sensor error
  • Water tank temperature sensor error
  • Insufficient water flow
  • Blocked water filter
  • Partially closed valve
  • Circulation pump malfunction
  • Incorrect temperature setting
  • Insufficient heating capacity

Recommended Checks

First, compare the controller’s displayed outlet water temperature with the actual measured temperature.If there is a significant difference:

  • Check the temperature sensor
  • Inspect the sensor wiring
  • Replace the sensor if necessary

If the sensor reading is accurate, continue checking:

  • Water filter
  • Valves
  • Circulation pump
  • Actual water flow
  • Water system resistance
  • Actual heat pump heating capacity

Recommended Solution

Do not simply increase the temperature setting to compensate for low outlet water temperature.

First confirm that the sensor, water flow, and heat pump operating conditions are normal.


2. Incomplete Defrosting

Typical Symptom

During heating operation, a significant amount of frost accumulates on the outdoor coil and remains after the defrost cycle, resulting in reduced heating performance.

Possible Causes

  • Incorrect temperature sensor position
  • Sensor reading error
  • Sensor wiring problem
  • Incorrect defrost parameters
  • Outdoor fan malfunction
  • Insufficient refrigerant
  • Insufficient airflow
  • Extremely low ambient temperature
  • Dirty outdoor heat exchanger

Recommended Checks

  1. Check the position of the relevant temperature sensors.
  2. Inspect the sensors and wiring.
  3. Compare sensor readings with actual temperatures.
  4. Check the defrost parameters.
  5. Check outdoor fan operation.
  6. Inspect the outdoor heat exchanger for dirt or blockage.
  7. If heating capacity has also dropped or low-pressure conditions are present, check the refrigerant system.

Important Note

Some frost formation during heating operation does not necessarily indicate a fault.

Under low-temperature and high-humidity conditions, frost formation on the outdoor coil is a normal part of heat pump operation.

The situation that requires attention is:

Persistent heavy frost + incomplete defrosting + significant reduction in heating capacity.


3. Circulation Pump Does Not Start

Typical Symptom

The heat pump has a heating or cooling demand, but the circulation pump does not operate, resulting in insufficient or zero water flow.

Possible Causes

  • Pump motor failure
  • Pump shaft blockage
  • Power supply problem
  • Pump relay failure
  • No control signal from the control board
  • Loose electrical connection
  • Pump protection activated

Recommended Checks

  1. Check whether the pump has power.
  2. Inspect the pump wiring.
  3. Confirm that the controller is sending a pump start signal.
  4. Check whether the pump shaft is mechanically blocked.
  5. Inspect the pump relay.
  6. Check the control board output.
  7. Confirm that pump flow and head meet the system requirements.

Recommended Solution

If the pump is mechanically blocked, it should be serviced or replaced by a qualified technician.

If the control board does not provide the required output signal, inspect the control circuit before replacing the board. If the relay is confirmed to be faulty, replace it with the appropriate component.


4. Why Is Water Flow So Important?

Water flow is one of the key parameters for stable air source heat pump operation.

Insufficient water flow can lead to:

  • Reduced heat transfer efficiency
  • Abnormal outlet water temperature
  • Reduced heating capacity
  • High-pressure protection
  • Unstable system operation

Therefore, when a system has insufficient heating capacity or cannot reach the target outlet water temperature, water flow should be one of the first things to check.

During installation, the following should be properly selected and designed according to the heat pump requirements:

  • Circulation pump
  • Pipe diameter
  • Pipe length
  • Valves
  • Filters
  • Water system layout

Even a high-performance heat pump cannot deliver its expected performance if the water system is incorrectly designed.


5. The Correct Troubleshooting Sequence

When a heat pump operates abnormally, it is not recommended to immediately open the unit or replace major components.

A more effective troubleshooting sequence is:

Step 1: Confirm Operating Conditions

Check:

  • Ambient temperature
  • Setpoint
  • Operating mode
  • Inlet water temperature
  • Outlet water temperature

Step 2: Check Water Flow

Confirm:

  • Pump operation
  • Actual water flow
  • Filter condition
  • Valve position
  • Water system resistance

Step 3: Check the Air Side

Confirm:

  • Outdoor fan operation
  • Outdoor heat exchanger
  • Air inlet and outlet clearance
  • Frost condition

Step 4: Check the Sensors

Confirm that controller readings match the actual temperatures.

Step 5: Check the Refrigerant System

If necessary, check:

  • Refrigerant pressure
  • Leakage
  • Restrictions
  • Refrigerant charge

Step 6: Check Major Components

Only after the basic system checks should you move on to:

  • Compressor
  • Control board
  • Contactors
  • Relays
  • Other electrical protection components

Check the system before replacing components.

This principle can improve diagnostic efficiency and reduce unnecessary component replacement.


6. How to Prevent Heat Pump Problems

Regular maintenance is usually more cost-effective than repairing a problem after it occurs.

Clean the Outdoor Heat Exchanger Regularly

Dust, leaves, and other debris can restrict airflow and reduce heat transfer efficiency.

Clean Water Filters Regularly

A blocked filter can reduce water flow and may trigger system alarms.

Check the Circulation Pump

Make sure the pump provides sufficient flow and head for the heat pump system.

Check Pipe Insulation

Proper insulation reduces heat loss and improves overall system efficiency.

Inspect Valves and Water Piping

Make sure valves operate correctly and water resistance is within the expected range.

Check Temperature Sensors

Periodically verify that sensor readings are accurate.

Maintain Sufficient Clearance Around the Outdoor Unit

Keep the air inlet and outlet free from obstructions to ensure proper airflow.

Advice for Installers and HVAC Contractors

For commercial and large-scale heat pump projects, maintenance should not begin only after a fault occurs.

A preventive maintenance program can help:

  • Reduce equipment failure
  • Minimize unplanned downtime
  • Maintain stable heating and cooling performance
  • Reduce long-term maintenance costs
  • Extend equipment service life

For larger projects, it is also useful to regularly record:

Ambient temperature + inlet water temperature + outlet water temperature + water flow + operating pressure + alarm history

Long-term operating data can help engineers identify potential problems before they become major failures.

Need Technical Support?

If you are an installer, distributor, HVAC contractor, or project engineer, you can provide the following information when troubleshooting a system:

  • Heat pump model
  • Unit capacity
  • Alarm code
  • Ambient temperature
  • Inlet / outlet water temperature
  • Pump and water flow information
  • Refrigerant pressure
  • Controller photos
  • Installation photos or videos

Complete operating information makes it easier to determine whether the problem comes from:the heat pump itself, the water system, the installation conditions, or the operating environment.

Professional troubleshooting is not only about repairing the equipment. It is also about ensuring that the heat pump continues to operate efficiently, reliably, and consistently over the long term.